Selecting a floating-operation power supply – voltage, battery and backup time
04/11/2026
Author: Andrzej Łapa
In many industrial devices and installations, a loss of the primary power supply must not interrupt the operation of connected equipment. During the design stage, it is therefore necessary to determine which loads must remain active, for how long and under what load conditions. If they must continue operating without interruption after a mains failure, a floating-operation power supply with a correctly selected battery is the appropriate solution.
When the 230 V AC mains supply is available and operating correctly, the power supply delivers energy to the loads while charging the battery and keeping it ready for use. If the mains supply fails, power is drawn from the battery. The control system monitors battery discharge, protects the battery against operation outside its permitted range and signals alarm conditions. In this way, the floating-operation power supply provides a guaranteed DC power source.
Output voltage in different operating modes
Floating-operation power supplies are available in 12, 24 and 48 V DC versions, among others. The choice of output voltage depends on the connected loads, required power and intended application. When selecting a power supply, it is also important to consider that the output voltage may vary depending on whether the unit is operating from the mains, the battery charging stage and whether power is currently being drawn from the battery.
A 24 V DC system illustrates this well, as its output voltage is directly linked to the battery voltage. It may vary from approximately 28.8 V during charging to around 21 V towards the end of battery operation. This is an inherent characteristic of this type of solution, so the designer should verify that all connected loads can operate correctly across the entire expected voltage range.
If some devices require a regulated voltage, the power supply can be equipped with an additional DC/DC converter. One example is the MERAWEX ZEM100, which, depending on the version, maintains a voltage of at least 24 V at a designated output even as the battery discharges. It can also provide additional outputs with voltages suited to other loads. This allows devices with different voltage requirements to be powered from a single system.
Which power supply should be used with a selected battery?
The battery type and capacity are usually determined by the required backup time and expected load. The power supply must provide sufficient power to supply the loads and charge the battery simultaneously. The power balance must account for the maximum load current, short-term inrush currents and the current allocated to battery charging. The latter determines how long it takes to recharge the battery after a period of battery operation.
Battery temperature also affects charging parameters. A sensor positioned near the battery sends temperature readings to the controller, which adjusts the voltage according to a predefined temperature compensation coefficient. This reduces the risk of overcharging at high temperatures and undercharging at low temperatures, helping to maintain the service life specified by the battery manufacturer.
The ability to set the voltage, limit the current and select an appropriate charging algorithm makes it possible to configure power supplies for use with VRLA AGM lead-acid batteries, LiFePO₄ batteries and other types of lithium batteries. For lithium battery packs, the power supply’s operating mode must also be coordinated with the battery management system (BMS), which protects the individual cells.
Battery monitoring during operation
When the power supply switches to battery operation, it draws energy from the battery while monitoring its voltage, signalling an approaching discharge limit and disconnecting the battery once a predefined threshold is reached. This protects the battery against deep discharge. In selected solutions, lower-priority loads can also be disconnected earlier, reserving the remaining energy for devices that require a longer backup time.
Voltage measurement alone, however, does not provide a complete picture of battery condition. A battery may show a normal open-circuit voltage and still fail to provide the required operating time. The power supply can therefore periodically check the battery’s behaviour under load and measure the resistance of the battery circuit. This helps detect not only battery deterioration but also problems with cables, terminals or the fuse. Resistance measurement supports diagnostics but does not replace a capacity test performed by controlled discharge.
Operating states can be indicated locally by LEDs, reported through relay contacts or transmitted via an RS-485 interface. This allows the supervisory system to receive information about mains failure, battery operation, overload or a fault in the battery circuit before the problem becomes apparent during a subsequent power failure.
A solution tailored to the specific application
A floating-operation power supply can take the form of a module designed for integration into a device under development or a complete power supply station incorporating batteries, protection devices, status indication and a suitable enclosure. The choice should be based on the load characteristics, required backup time, battery technology, environmental conditions and communication requirements.
Before selecting a device, it is therefore necessary to determine the load voltage and maximum current, the permissible operating voltage range, the required backup time, the battery technology and capacity, and the diagnostic functions needed. MERAWEX designs both modular floating-operation power supplies and complete guaranteed DC power supply systems, allowing solutions to be tailored to the specific device, load and actual operating conditions.
Other technical articles
How to plan a power supply system replacement without risking continuity of operation?
08/09/2026
Key principles for replacing a power supply system in an operational facility
ZM power supplies – how to select the right version for your application
12/10/2026
Overview of the ZM power supply range: from AC/DC modules and redundant configurations to floating-operation power supplies and high-power systems, compact DC power systems, ZMS stations with batteries, and DC/DC converters.
Uninterruptible Power Supply for Telecommunications and Remote Control Systems – How to Design a System for Power Outages
25/08/2026
Selecting floating-operation power supplies for telecommunications and telecontrol systems – key principles of system design, battery backup and monitoring
Select a floating-operation power supply and battery to meet your application requirements
Do you need a floating-operation power supply tailored to the requirements of your device or installation? Contact us – we will help you select the power supply, battery and charging system parameters for your specific application.
-
1
After receiving your enquiry, we will contact you by phone or email.
-
2
During the call, we will discuss your requirements and propose suitable solutions.
-
3
If necessary, we will arrange additional technical consultations.
-
4
We approach each case individually, so you can be sure that our response will be tailored to your requirements.