Guaranteed 24 V DC power supply in the power industry – how to ensure continuity of substation automation and telecontrol systems?
03/09/2026
Author: Andrzej Łapa
At an electrical substation, a loss of 24 V DC power is not simply a power supply problem. It can result in loss of communication with the facility, controller restarts, inability to control switchgear and, consequently, difficulties in monitoring substation operation and carrying out switching operations.
Therefore, when designing a power supply system for substation automation, it is not enough to specify the required power supply capacity. It is also necessary to check how the system will behave following an AC power failure, how it monitors the battery, whether it can withstand the conditions at the substation and how it communicates information to the supervisory system.
What can a loss of 24 V DC power cause?
Modern electrical substations use numerous automation, telecontrol, protection and communication devices. 24 V DC may be used to power, among other things, bay controllers, RTUs, protection and control devices, data concentrators, protocol converters and data transmission equipment connected to the SCADA system.
Their proper operation depends not only on the presence of voltage, but also on the continuity and stability of the power supply.
A short-term AC power failure or voltage dip can cause a controller or telecontrol terminal to restart. This can result in a temporary loss of remote monitoring and control of the facility. If the 24 V DC supply also powers control circuits, the problem may affect the execution of commands to switch switchgear on or off.
From an operational perspective, this means that the auxiliary power supply system must continue to operate even when the primary energy source is no longer available.
A power supply with a battery is not always sufficient
The simplest way to provide power during an AC mains failure is to use a power supply connected to a battery. In a floating-operation system, the rectifier, battery and loads are connected in parallel.
During normal operation, the rectifier supplies the loads and keeps the battery charged. When the AC supply fails, the battery takes over without any interruption associated with switching between power sources.
However, the mere presence of a battery does not guarantee that the system will provide the required backup time.
Batteries gradually lose capacity, and their internal resistance may increase. The battery circuit may also become disconnected, or a protection device may fail. If the system does not monitor these conditions, a fault may remain undetected until the primary power supply fails.
During normal operation, the problem may remain undetected because the loads are supplied by the rectifier. A battery fault only becomes apparent when the AC supply fails and the battery is unable to provide the required backup time.
Therefore, in power infrastructure applications, not only the rectifier parameters are important, but also battery circuit diagnostics and battery management.
How should a 24 V DC guaranteed power supply system operate?
A DC power system integrates rectification, battery charging, voltage distribution, protection, diagnostics and communication functions. This allows the individual components to operate as a single monitored system.
The basic components of such a solution are:
- rectifier modules,
- a controller responsible for system operation and battery charging,
- DC circuit distribution and protection,
- a battery bank,
- battery circuit diagnostics,
- communication with the supervisory system.
Under normal conditions, the rectifiers supply the loads and charge the battery. When the AC supply fails, the loads remain powered by the battery, without any interruption caused by switching between power sources. However, system reliability depends not only on the architecture itself, but also on how each function is implemented.
Temperature compensation of the charging voltage
Batteries used in electrical substations may operate over a wide temperature range. The charging voltage should therefore be adjusted to the battery temperature.
Temperature compensation reduces the risk of overcharging at elevated temperatures and undercharging at low temperatures.
Protection against deep discharge
A prolonged AC power failure can lead to excessive battery discharge. The RGR function disconnects the battery from the loads when the configured voltage threshold is reached.
This prevents further battery discharge and reduces the risk of permanent damage.
Battery diagnostics
Monitoring the voltage of the entire battery alone does not always allow a problem to be detected early enough. Therefore, the system should monitor, among other things, the continuity of the battery circuit, the status of protection devices and the voltage balance between series-connected battery blocks.
For maintenance personnel, this means that a fault can be detected before the primary power supply fails.
Rectifier redundancy
In systems where power interruptions are unacceptable, a single rectifier module may not be sufficient.
An N+1 configuration allows independent modules to operate in parallel. If one module fails, the remaining modules continue to supply the loads and, provided that the adopted power balance allows it, charge the battery. A hot-swap design allows a faulty module to be replaced without shutting down the entire DC power system.
Remote monitoring
For distributed power infrastructure, manually checking each device increases maintenance costs and extends response times when a fault occurs.
Therefore, the DC power system should transmit information on voltages, currents, battery status, alarms and events to the supervisory system. This allows maintenance personnel to continuously assess the power supply status and respond more quickly to abnormalities.
Operating conditions at the substation matter
Devices may be installed in outdoor cabinets, containerised transformer substations or unheated rooms. Temperature, humidity and limited installation space affect both the electronics and the battery service life and thermal balance of the cabinet.
The electromagnetic environment is also important. Switching operations in high- and medium-voltage networks, overvoltages and lightning strikes can cause interference in auxiliary circuits. In such conditions, the device’s immunity to electromagnetic disturbances, proper cable routing and the required galvanic isolation of interfaces are important.
Therefore, the selection of a DC power system should take into account not only the load current, but also the installation location, operating temperature, mounting method and communication requirements.
SI24D and SI24-3U – 24 V DC power supply systems
For powering bay controllers, protection and control devices, telecontrol equipment and data transmission equipment, MERAWEX offers the SI24D and SI24-3U DC power systems.
The devices are designed for installation in substation automation and telecommunications cabinets. The 19″ RACK design is available in 1U, 2U and 3U versions. In SI24D devices, the cassette depth does not exceed 320 mm, making installation easier in cabinets with limited space.
Selected configurations:
| Model | Height | Output voltage | Output current | Output power |
| SI24D-1U2-251-ET | 1U | 24 V DC, 27,1 V in float operation | 25 A | 600 W |
| SI24D-1U2-252-ET | 1U | 24 V DC, 27,1 V in float operation | 50 A | 1200 W |
| SI24D-2U2-252-ET | 2U | 24 V DC | 50 A | 1200 W |
| SI24-30-32 | 3U | 24 V DC | 30 A | 750 W |
| SI24-30-33 | 3U | 24 V DC | 30 A | 750 W |
| SI24-40-42 | 3U | 24 V DC | 40 A | 960 W |
| SI24-40-43 | 3U | 24 V DC | 40 A | 960 W |
Depending on the version, the systems are available with a single rectifier or multiple modules operating in parallel. SI24D models use hot-swap modules, allowing an individual rectifier to be replaced without shutting down the system.
Efficiency and operating temperature
The power systems use switching-mode rectifiers with active power factor correction (PFC). Efficiency exceeding 93% reduces energy losses and heat generation.
This is particularly important in enclosed cabinets, where heat dissipation is limited.
The declared operating temperature range for SI24D devices is −33°C to +70°C. This allows them to be used in locations where conditions extend beyond those typically found in heated technical rooms.
When selecting a device for a specific facility, however, the actual installation conditions, any power derating at extreme temperatures and the cabinet’s thermal balance should be taken into account.
Battery diagnostics and communication with the supervisory system
In a guaranteed power supply system, output voltage information alone is not sufficient to assess system readiness.
SI24D power systems support AGM, gel and LiFePO₄ batteries. The controller provides, among other functions, automatic charging with current limiting, temperature compensation of the charging voltage, monitoring of battery circuit continuity and battery symmetry, and protection against deep discharge.
The available interfaces allow the monitoring method to be adapted to the facility’s infrastructure. Ethernet with a web server provides access to device parameters, SNMP enables integration with the monitoring system, while RS-485 supports communication via the Modbus RTU protocol.
Depending on the version, a local USB interface or an optical IR port compatible with the S128-IR head is also available.
MeraSI software is used for device diagnostics and parameter configuration. For a larger number of distributed facilities, the SIMON4 system enables central monitoring of DC power systems, parameter logging and alarm indication.
The controller can store up to 6,000 events in non-volatile memory. The event history facilitates the analysis of disturbances and helps determine how the system parameters changed before an alarm or failure occurred.
When 110 or 220 V DC is available at the substation
Not every substation requires 24 V DC to be generated directly from an AC supply. Larger facilities may already have a guaranteed 110 or 220 V DC supply available. In such cases, 24 V DC circuits can be powered using DC/DC converters.
For this purpose, MERAWEX offers high-power DC/DC converters from the ZM-DC series, including the ZM-DC4-24V48A. They convert 110 or 220 V DC into 24 V DC and provide galvanic isolation.
For smaller automation systems, the ZEM series power supplies are available for mounting on TS35 DIN rails.
This approach makes it possible to use the existing guaranteed power supply infrastructure and derive 24 V DC circuits from it without building another independent battery-backed system.
What are the benefits of the right architecture?
A well-designed 24 V DC power supply system not only reduces the likelihood of failure, but also limits its consequences and the time required to detect a fault.
In practice, this means:
- continuity of power supply to the loads following an AC power failure,
- reduced risk of losing monitoring and control of substation equipment,
- earlier detection of battery and battery circuit problems,
- remote monitoring of parameters, alarms and events,
- fewer unplanned interventions at distributed facilities,
- the possibility of using rectifier redundancy,
- faster diagnostics through event logging,
- equipment adapted to the available cabinet space,
- the use of an existing 110 or 220 V DC system to power 24 V DC circuits.
The device should be selected based on the actual load profile, required autonomy, battery type, environmental conditions and method of integration with the supervisory system.
How to select a 24 V DC power supply system?
The selection of a DC power system should begin with an analysis of the specific facility. At a minimum, the following should be determined:
- Maximum and typical DC load – including starting currents and transient loads.
- Required backup time – based on the type of loads and the required autonomy of the facility.
- Battery type, voltage and configuration.
- Temperature conditions, mounting method and cabinet thermal balance.
- Required level of rectifier redundancy.
- Required diagnostics and method of communication with the supervisory system.
- Available installation space and cable routing arrangements.
- Existing guaranteed power supply architecture, such as 110 or 220 V DC.
Based on this information, the appropriate architecture can be selected: a 24 V DC power system with a battery, a system with redundant rectifiers, or a DC/DC converter supplied from an existing 110 or 220 V DC distribution system.
In power infrastructure, 24 V DC supplies devices responsible for monitoring, control, protection and communication. Therefore, the design should cover not only the power balance and required backup time, but also battery diagnostics, resistance to environmental conditions, redundancy and the method of transmitting alarms.
SI24D, SI24-3U, ZM-DC converters and ZEM power supplies make it possible to select a solution for both a single automation cabinet and a distributed system covering multiple facilities.
Other technical articles
Uninterruptible Power Supply for Telecommunications and Remote Control Systems – How to Design a System for Power Outages
25/08/2026
Selecting floating-operation power supplies for telecommunications and telecontrol systems – key principles of system design, battery backup and monitoring
How to plan a power supply system replacement without risking continuity of operation?
08/09/2026
Key principles for replacing a power supply system in an operational facility
From SI48-10 to modern DC power systems – the development of telecommunications power supply technology
11/08/2026
Changes in telecommunications power systems: from the SI48-10 rectifier to modern SI48 DC power systems
Ask about 24 V DC guaranteed power supply
Do you need to ensure continuity of substation automation and telecontrol systems after an AC power failure? Send us your installation requirements, load and required backup time, and we will select the appropriate DC power system, battery or converter for the operating conditions of the facility.
-
1
After receiving your enquiry, we will contact you by phone or email.
-
2
During the call, we will discuss your requirements and propose suitable solutions.
-
3
If necessary, we will arrange additional technical consultations.
-
4
We approach each case individually, so you can be sure that our response will be tailored to your requirements.