ZUP-230V (230Vac / 400-1500W)

ZUP-230V-BM-1000S

Mains voltage 230V
Nominal output voltage 230Vac
Nominal output voltage 230Vac
Power 1000W
Output No. 1
Battery capacity 2x 18/22Ah 12V

The main application of the ZUP-230V-BM power supplies includes:

  • 230V voltage supply for aeration gates of gravity smoke exhaust systems
  • powering other devices requiring a guaranteed voltage of 230V, and optionally 24Vdc

 

The ZUP-230V-BM power supplies are used to supply uninterruptible voltage of 230Vac and optionally 24Vdc to devices:

  • Fire signaling according to EN 54-4 + A1 + A2
  • Smoke and heat control according to EN 12101-10
  • Fire protection according to Reg. Ministry of Interior and Administration of June 20, 2007 (Journal of Laws No. 143, item 1002, amended, Journal of Laws No. 85, item 553 of April 27, 2010)

The certificate of constancy of performance issue by CNBOP-PIB No. 1438-CPR-0761

  • immunity to difficult operating conditions (-5 ... +40°C)
  • a metal hanging cabinet with a lock, contains a battery of two batteries
  • temperature compensation of floating operation voltage and bulk charging voltage
  • battery circuit resistance monitoring
  • AC 230V voltage output
  • relay output (normally open) for switching on fire protection devices
  • possibility of accepting a fire alarm from FCP (fire control panel)
  • output remote relay signal with collective fault to FCP
  • the possibility of setting the delay of switching on the DC / AC 230V converter in relation to the fire alarm appearance
  • ability to set the working time of the 230V DC / AC converter output
  • supervision up to 72 hours
  • LED indicator of the power supply operation status
  • remote signaling: collective fault signal (three relay contacts available)
  • internal LVDD
  • external fire alarm input
  • input of a manual gate opening switch 